Техническое чтение для энергетиков. Бухарова Г.П. - 34 стр.

UptoLike

Составители: 

36
* but it is a further 120° behind in phase но она (эдс) еще на 120° отстает по фазе
TRANSMISSION OF THREE-PHASE POWER
The three windings discussed above can be made to supply three individual circuits,
when all six ends must be used. It is possible, however, to link the three circuits
electrically with the result that the number of conductors necessary for the
transmission of the power is reduced.
In the first instance it is possible to effect an economy by using a common return, this
being permissible since it does not disturb the electrical arrangement. This implies
that the three rear ends of the turns, A', B', and С' must all be joined, together with the
three rear ends of the three resistances used as loads. This arrangement is illustrated
in Fig. 7 which shows the three generator windings connected together at one end, the
other ends being connected to three conductors for the purpose of transmitting the
power. The return conductor carries the vector sum of these three currents back to the
common junction of the three generator windings.
If the three e. m. f. s are all equal and the three load resistances are also all equal, the
three currents will also be all equal and will have a phase difference of 120° from one
another. In these circumstances the system is said to be balanced.
Fig. 7. Transmission of Three-Phase
Power by Four Conductors
Fig. 8. Transmission of Three- Phase
Power by Three Conductors
Three-Wire Transmission. – In a balanced three-phase system the three currents are
equal and can be represented by the graphs shown in Fig. 6, substituting current for e.
m. f. The resultant current in the tourth (return) conductor is, at any instant, the
algebraic sum of the three line currents and, on examination of the graphs, it is found
that this algebraic sum is zero at every instant. The fourth (return) conductor thus
carries no current and it can be omitted. The connections now take the form shown in
Fig. 8, three conductors only being employed.
Each conductor now acts in turn as the return for the other two. This can be checked
from Fig. 6, where it is seen that the reverse current in one phase is always equal to
the forward current in the other two. (At certain instants, two conductors act as the
return for the forward current in the remaining conductor). It is also general practice